PART IV: SOLAS CHAPTER II-2 Construction – Fire protection, fire detection and fire extinction

Previous Page | Next Page

1 GENERAL

1.1 Definitions

1.1.1 The following definitions are applicable to this chapter:

  1. "Equipment" includes appliances.
  2. "FSS Code" means the International Code for Fire Safety Systems, published by the IMO.
  3. "FTP Code" means the International Code for Application of Fire Test Procedures, 2010, published by the IMO.

2 FTP CODE AND FSS CODE

2.1 Material, Equipment, and System Approval

2.1.1.1 All material, equipment and system required approval shall be approved in accordance with TP 14612: Procedures for Approval of Life-Saving Appliances and Fire Safety Systems, Equipment and Products.

2.1.1.2 If materials must be approved by the Minister as meeting requirements set out in the FTP Code:

  1. The Minister's approval is not required when section 6 of the FTP Code applies, and
  2. The FTP Code applies in respect of the Minister's approvals of the materials, except that the Code is to be read without reference to the words "In general".

2.2 Clarification: FTP Code

2.2.1.1 For the purpose of this document, the following modifications to the FTP code are applicable:

  1. "May" is to be read as "must" in section 3.4 of Part 3 of Annex 1 to the FTP Code,
  2. Section 3.5.2.1 of Part 3 of Annex 1 to the FTP Code is to be read as "Thermal radiation through windows must be tested and evaluated in accordance with appendix 3 to this part if escape routes pass near the windows", and
  3. The hose-stream test procedure set out in section 5 of appendix 2 to Part 3 of Annex 1 to the FTP Code is mandatory if escape routes pass near the windows.

2.2.1.2 For "A" class divisions" the insulation on the decks and bulkheads is to be held in place in accordance with the certificate of approval and manufacturer's instructions by closely spaced studs and clips, or by other means, that will hold the insulation in place taking into account the vibration and motion of the vessel and the normal wear.

3 REGULATIONS

3.1 Regulation 4 - Probability of Ignition

3.1.1 Oil Fuel Tanks

3.1.1.1 For the purposes of regulation 4.2.2.3.5.1, if sounding pipes are used they must terminate on an open deck, if feasible.

3.1.2 Prevention of Overpressure

3.1.2.1 For the purposes of regulation 4.2.2.4, the air pipes on any oil tank or part of the oil fuel system must be flame-screened and terminate on an open deck, if feasible.

3.1.3 Ventilation Systems in Cargo Pump-rooms

3.1.3.1 The mechanical ventilation system required by regulation 4.5.4.1 must:

  1. Permit the extraction of air from the cargo pump room bilges immediately above the transverse floor plates or bottom longitudinals,
  2. Have an emergency intake that is:
    1. Situated in the ventilation ducts at a height of at least 2 m above the lower platform of the cargo pump room, and
    2. Fitted with a fire damper that is capable of being opened and closed from the weather deck or the lower platform of the cargo pump-room.
  3. Provide a means of ensuring a free flow of gases through the lower platform of the cargo pump-room to the ventilation duct intakes.

3.2 Regulation 5 - Fire Growth Potential

3.2.1 Closing Appliances and Stopping Devices of Ventilation

3.2.1.1 In addition to the requirements of regulation 5.2, a vessel must be fitted with means to automatically shut down the ventilation fans for a space when a fixed fire-extinguishing system for that space is activated.

3.2.1.2 In addition to the requirements of regulation 5.2.2.3, a vessel must be fitted with means of control if the vessel is provided with any other equipment, such as hydraulic power systems, that could create a fire or any other danger in the space.

3.2.2 Insulating Materials

3.2.2.1 In addition to the restriction in regulation 5.3.1.1 on the use of combustible insulating materials, organic foam must not be used in the mail rooms or baggage rooms of a passenger vessel.

3.2.2.2 If organic foam is used in a cargo space or a refrigerated compartment of a service space:

  1. The exposed surfaces of the foam must be:
    1. sealed with an intumescent coating that is approved by the Minister as meeting the flame-spread, smoke and toxicity requirements set out in Annex 1 to the FTP Code, and
    2. covered with a steel-sheet protective facing.
  2. In the case of organic foam used in a refrigerated cargo space or a refrigerated compartment of a service space on a vessel of steel construction, the boundaries to the space must be of steel construction, and
  3. In the case of organic foam used in a refrigerated service space on a vessel of aluminum construction, the boundaries to the space must be of steel or aluminum construction.

3.2.3 Trunks and Ducts of Ventilation Systems

3.2.3.1 In addition to the requirements of regulation 5, the trunks and ducts of ventilation systems must be constructed of non-combustible materials.

3.2.3.2 If a trunk or duct serves spaces on both sides of a deck or bulkhead of "A" class divisions, fire dampers must be fitted so as to prevent the spread of fire and smoke between compartments. Manual fire dampers must be operable from both sides of the deck or bulkhead.

3.2.3.3 If a trunk or duct has a free cross-sectional area that exceeds 0.02 m2 and passes through a deck or bulkhead of "A" class divisions, the trunk or duct must be fitted with a fail-safe automatic-closing fire damper.

3.2.3.4 If a trunk serves compartments situated on only one side of a deck or bulkhead of "A" class divisions, the opening in the deck or bulkhead must be lined with a steel sheet sleeve unless the ducts passing through the deck or bulkhead are of steel in the vicinity of the passage and the portion of the trunk in that vicinity:

  1. Has sleeves that are at least 3 mm thick and 900 mm long and is provided with fire insulation that has at least the same fire integrity as the deck or bulkhead, if the free cross-sectional area of the ducts is more than 0.02 m2, or
  2. Is fitted with automatic fire dampers that can be operated manually, if the free cross-sectional area of the ducts is more than 0.085 m2.

3.2.3.5 A sleeve referred to in paragraph 3.2.3.4 that passes through a bulkhead must be of the same length on either side of the bulkhead.

3.2.3.6 Paragraph 3.2.3.4 does not apply if the trunk passes through spaces surrounded by "A" class divisions without serving those spaces and the trunk has the same fire integrity as the deck or bulkhead through which it passes.

3.2.4 Low Flame-Spread Characteristics of Exposed Surfaces

3.2.4.1 The requirements of regulation 5.3.2.4 apply to plastic piping in accommodation and service spaces and control stations and must be approved by the Minister as meeting the flame-spread requirements set out in Annex 1 to the FTP Code.

3.3 Regulation 6 - Smoke Generation Potential and Toxicity

3.3.1 Plastic Piping

3.3.1.1 In addition to the requirements of regulation 6, the plastic piping in accommodation and service spaces and control stations must be approved by the Minister as meeting the smoke and toxicity requirements set out in Annex 1 to the FTP Code.

3.3.1.2 Paragraph 3.3.3.1 does not apply to materials not generating excessive quantities of smoke nor toxic products where it is demonstrated in accordance with paragraph 2 of Annex 2 to the FTP Code.

3.4 Regulation 7 - Detection and Alarm

3.4.1 Smoke Detectors

3.4.1.1 In addition to the requirements of regulation 7.5, a smoke detector must be installed in every cabin and every service space, regardless of the method of fire protection chosen.

3.4.2 Protection of Cargo Spaces in Passenger Vessels

3.4.2.1 For the purposes of regulation 7.6, the expression "where it is shown to the satisfaction of the Administration that the ship is engaged on voyages of such short duration that it would be unreasonable to apply this requirement" is to be read as "in the case of voyages of not more than 48 hours' duration during which the cargo holds are opened to load or unload cargo."

3.4.3 Fire Patrols in Passenger Vessels

3.4.3.1 Regulation 7.8.1 applies in respect of a vessel that is not a Safety Convention vessel only if it:

  1. Is carrying more than 25 berthed passengers or more than 50 passengers, or
  2. Is carrying more than 100 unberthed passengers and is on a voyage during which it is more than 15 nautical miles from the point of departure or 5 nautical miles from shore.

3.4.3.2 The fire patrols required by regulation 7.8.1 must be performed at least once every hour and include a patrol of the entire vessel.

3.4.4 Passenger Vessels at Dock

3.4.4.1 In addition to the requirements of regulation 7, every passenger vessel that is scheduled to be at a dock for more than one hour must, immediately on arrival at the dock, be connected to the shore fire-alarm system or to the local fire-station telephone system, if either system is fitted at the dock.

3.5 Regulation 9 - Containment of Fire

3.5.1 Protection of Stairways and Lift Trunks in Accommodation Spaces, Service Spaces and Control Stations

3.5.1.1 The class divisions requirements of regulation 9.2.3.4 for stairways and lift trunks that penetrate more than a single deck apply to any area, such as a landing or corridor, between the stairways or lift trunks, if feasible.

3.5.1.2 To provide a much safer means of escape and access for fire parties, the stair tower arrangement as per figure 1 of regulation 9.2.3.4.1 in the appendix of MSC Circular 1120 (MSC/Circ.1120) should be provided unless it is not feasible. If multiple stairways are arranged to connect several decks using the arrangement shown in figure 2.1 and 2.2 in the appendix of MSC/Circ.1120, the occupants must leave the protected enclosure at every other level and could be exposed to heat and smoke while transiting the intervening deck areas. (See also Regulation 13).

3.5.2 Openings in Decks and Bulkheads in Passenger Vessels

3.5.2.1 In addition to the requirements of regulation 9.4.1.1.2, the following requirements must be met:

  1. Every door in an "A" class division must:
    1. overlap the door frame at the top and sides and allow for a gap, between the edges of the door and the door frame, that is the minimum needed to open and close the door. Except as provided in iii, the gap at the bottom of the door should be the minimum needed to open and close the door and in no case more than 12 mm,
    2. be reasonably gastight if the door is fitted between a machinery space and an accommodation space, and
    3. when fitted on a stairway enclosure, a main vertical zone or an escape route, have a gap at the bottom that is the minimum needed to open and close the door, in order to reasonably prevent the ingress of smoke.
  2. Grilles or louvres must not be fitted in a door in an "A" class division.

3.5.2.2 The hose port requirements of regulation 9.4.1.1.7 apply in respect of every hose port fitted in a door in an "A" class division.

3.5.2.3 If a ventilation duct passes through a main horizontal zone division on a passenger vessel, a fail-safe automatic-closing fire damper must be fitted in accordance with regulation 9.4.1.1.8, and the duct between the division and the damper must meet the requirements of that regulation.

3.5.2.4 In addition to the requirements of regulations 9.4.1.1 and 9.4.1.2, every door in an "A" or "B" class division must be fitted with a thin metal identification plate that:

  1. Has clearly stamped on it the door manufacturer's name, the "A" or "B" class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured, and
  2. Is screwed or riveted to either of the vertical edges of the door panel.

3.5.3 Doors in Fire-resisting Divisions in Cargo Vessels

3.5.3.1 In addition to the requirements of regulation 9.4.2.1, the following requirements must be met:

  1. Every door in an "A" class division must:
    1. overlap the door frame at the top and sides and allow for a gap, between the edges of the door and the top, bottom and sides of the door frame, that is the minimum needed to open and close the door. Except as provided in iii, the gap at the bottom of the door should be the minimum needed to open and close the door and in no case more than 12 mm,
    2. be reasonably gastight if the door is fitted between a machinery space and an accommodation space, and
    3. when fitted on a stairway enclosure, have a gap at the bottom that is the minimum needed to open and close the door, in order to reasonably prevent the ingress of smoke.
  2. Grilles or louvers must not be fitted in a door in an "A" class division, and
  3. Every door in an "A" or "B" class division must be fitted with a thin metal identification plate that:
    1. has clearly stamped on it the door manufacturer's name, the "A" or "B" class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured, and
    2. is screwed or riveted to either of the vertical edges of the door panel.

3.5.3.2 For the purposes of regulation 9.4.2.2, if hold-back arrangements fitted with remote-release devices of the fail-safe type are utilized:

  1. The arrangements must be capable of being operated at the door and from the wheelhouse, and
  2. A fire door open-close indicator panel must be provided in the wheelhouse.

3.5.4 Protection of Openings in Cargo Pump-rooms

3.5.4.1 In addition to the requirements of regulation 9.5.2.6, a vessel that has cargo pump-rooms must not be fitted with windows in the boundaries of those rooms.

3.5.5 Ventilation Systems

3.5.5.1 An automatic fire damper required by regulation 9.7.2.1 to be fitted in a galley ventilation duct must be of a fail-safe design and be capable of being manually operated from both sides of the division through which the duct passes.

3.5.5.2 Despite regulation 9.7.2.1, the galley ventilation systems on all vessels must be separate from the ventilation systems serving other spaces.

3.5.5.3 The enclosures of stairways penetrating more than one deck must be fitted with ventilation systems that are separate from the ventilation systems serving other spaces.

3.5.6 Details of Ventilation Duct Penetrations

3.5.6.1 Despite regulation 9.7.3.1, ventilation ducts with a free cross-sectional area equal to, or less than, 0.02 m2 that pass through "A" class bulkheads or decks must, instead of meeting the requirements of that regulation that apply to those ducts, meet the requirements of that regulation that apply to ducts with a free cross-sectional area exceeding 0.02 m2 but not exceeding 0.075 m2.

3.5.6.2 If a ventilation duct passes through a bulkhead, ceiling or lining of "B" class divisions:

  1. If the duct is more than 0.075 m2 in free cross-sectional area, it must, despite regulation 9.7.3.2:
    1. be made of steel or other equivalent material that is at least 3 mm thick, or
    2. be lined with a steel sleeve at least 3 mm thick and at least 900 mm long divided equally on each side of the bulkhead, ceiling or lining.
  2. If the duct is more than 0.02 m2 and not more than 0.075 m2 in free cross-sectional area, it must, despite regulation 9.7.3.2:
    1. be made of steel or other equivalent material that is at least 1 mm thick, or
    2. be fitted with a steel sleeve at least 1 mm thick and at least 900 mm long divided equally on each side of the bulkhead, ceiling or lining.
  3. If the duct is not more than 0.020 m2 in free cross-sectional area, it must:
    1. be made of steel or other equivalent material that is at least 1 mm thick, or
    2. be fitted with a steel sleeve at least 1 mm thick and at least 200 mm long divided equally on each side of the bulkhead, ceiling or lining.
  4. The duct or, if a steel sleeve is fitted, the sleeve must be collared to the division with steel collars, and
  5. If a steel sleeve is fitted, the gap between the sleeve and the duct must be fully packed with a non-combustible material and the sleeve's ends must be sealed with a fire-retardant flexible sealant.

3.5.6.3 If a ventilation duct passes through a "B-15" class division, the duct's sleeve or spigot must be:

  1. Insulated on one side of the division for at least 380 mm from the division with mineral wool insulation of "A-15" standard that is approved by the Minister as meeting the fire test requirements for "A-15" class divisions set out in Annex 1 to the FTP Code, and
  2. Securely attached.

3.6 Regulation 10 - Fire Fighting

3.6.1 Fire-extinguishing Systems and Equipment

3.6.1.1 The fire-extinguishing systems and equipment required by regulation 10 and for which that regulation requires compliance with the provisions of the FSS Code must be of a type approved by the Minister as meeting the applicable requirements of that Code.

3.6.1.2 Paragraph 3.6.1.1 does not apply in respect of the design of pressure containers for a fixed fire-extinguishing system. Every pressure container for a fixed fire-extinguishing system must bear a mark indicating that it:

  1. Meets the applicable requirements for transport by road or ship that are set out in section 5.10 of the Transportation of Dangerous Goods Regulations,
  2. Meets the applicable requirements for transport by road or ship that are set out in Title 49, subpart C of part 178 of the Code of Federal Regulations of the United States, or
  3. Meets the applicable requirements for transportable pressure equipment that are set out in the Council of the European Union Directive 1999/36/EC and has undergone a conformity assessment procedure in accordance with that Directive by a notified body designated by a Member State of the European Union.

3.6.2 Water Supply Systems

3.6.2.1 The pipes, valves and fittings used with the equipment required by regulation 10.2:

  1. Must be made of corrosion-resistant metal or galvanized steel, and
  2. Must not be readily rendered ineffective at the anticipated low ambient temperatures or by heat from a fire.

3.6.3 Isolating Valves

3.6.3.1 If the fire main is an integral part of a fixed deck foam fire-extinguishing system with monitors, the isolating valves required by regulation 10.2.1.4.1 must be fitted immediately forward of each monitor.

3.6.3.2 In addition to the isolating valves required by regulation 10.2.1.4.1, valves must be fitted to sections of the fire main that:

  1. Are subject to freezing,
  2. Could be damaged because of a fire or explosion, or
  3. Might not be required when any other part of the fire main is used.

3.6.3.3 The valves required by paragraph 3.6.3.2 must be:

  1. Operable from positions that are easily accessible and protected from freezing, fire and explosions, and
  2. Clearly marked.

3.6.3.4 Every valve fitted to fire piping must be designed to open with a counter-clockwise rotation of the valve's handle.

3.6.3.5 The requirements of regulation 10.2.1.4.4 apply in respect of combination carriers.

3.6.4 Number and Position of Hydrants

3.6.4.1 Despite regulation 10.2.1.5.1, on a cargo vessel of less than 500 gross tonnage or on a passenger vessel of less than 500 gross tonnage that is not a Safety Convention vessel, the number and position of hydrants must be such that one jet of water can reach any part of the vessel.

3.6.4.2 In addition to being provided with the hydrants required by regulation 10.2.1.5.1:

  1. A passenger vessel on a near coastal voyage, Class 1 or an unlimited voyage and a vessel of 500 gross tonnage or more must be provided, in each machinery space of category A, with one hydrant on the port side and one hydrant on the starboard side, and
  2. Any other vessel of less than 500 gross tonnage must be provided with one hydrant in each machinery space of category A.

3.6.4.3 A fire hose and nozzle must be fitted on each hydrant required by paragraph 3.6.4.2.

3.6.4.4 If the size or configuration of a machinery space of category A would render a hydrant required by paragraph 3.6.4.2 ineffective, the hydrant must be located near the main access to the space.

3.6.4.5 In addition to being provided with the hydrants required by regulation 10.2.1.5.1, a cargo vessel of 2 000 gross tonnage or more must:

  1. Be provided with a hydrant in the shaft tunnel, if any, adjacent to the engine room watertight door, and
  2. Meet the requirements of regulation 10.2.1.5.2.2.

3.6.4.6 Every fire hydrant must be installed so that:

  1. A fire hose can be easily connected to it,
  2. It is limited to any position from the horizontal to the vertical pointing downward, so that the fire hose will lead downward or horizontally in order to minimize the possibility of kinking, and
  3. There is sufficient clearance below it to accommodate the radius of bend of the fire hose under pressure and to allow deployment of the hose in every direction.

3.6.5 International Shore Connection

3.6.5.1 The international shore connection required by regulation 10.2.1.7 must be stored on the vessel so as to be easily accessible. A notice in English and French indicating the connection's location and the maximum working pressure of the piping system must be posted on the vessel.

3.6.6 Fire Pumps

3.6.6.1 In addition to the requirements of regulation 10.2.2, the following requirements must be met in respect of a vessel's fire pumps:

  1. If the vessel is fitted with two or more power-driven fire pumps, a non-return valve must be fitted to the discharge line of each pump to prevent water from backing through the pump when it is not operating,
  2. A power-driven fire pump must be self-priming and fitted with pressure gauges on their suction and discharge sides,
  3. A manual fire pump must be operable without the need for manual priming and must be capable of delivering a jet of water of at least 12 m,
  4. A fire pump's sea connection must have arrangements to prevent blockage of the connection's inlet by ice and slush, and
  5. A fire pump must not have a rotor-impeller that can be damaged by heat from the pump or by the pump running dry.

3.6.6.2 If a bilge pump is to be used as a fire pump as permitted by regulation 10.2.2.1, the bilge pumping system and the fire pumping system must be capable of simultaneous operation.

3.6.6.3 One of the fire pumps required by regulation 10.2.2.2 may be manually operated on a vessel that is not a Safety Convention vessel, is of less than 1 000 gross tonnage and, in the case of a passenger vessel, is engaged on a sheltered waters voyage or a near coastal voyage, Class 2. If one of those pumps is manually operated and is located outside the space where the other fire pump required by that regulation and its source of power are located, the manually operated fire pump may also be used for the emergency fire pump if one is required by regulation 10.2.2.3.1.2.

3.6.6.4 A power-driven fire pump that is not required by regulation 10.2.2.2.2 to be independently driven on a vessel of less than 1 000 gross tonnage must not be powered by a main engine unless the engine can be operated independently of the propeller shafting.

3.6.6.5 Despite regulation 10.2.2.2.2 and paragraph 3.6.6.3, if a cargo vessel to which that subsection applies is engaged on a sheltered waters voyage or a near coastal voyage, Class 2:

  1. Only one independently driven fire pump is required to meet the requirements of that regulation and it must be power-driven, and
  2. Regulation 10.2.2.3.1.2 does not apply.

3.6.6.6 For the purposes of regulation 10.2.2.4.2:

  1. The expression "in any event be capable of delivering at least the two required jets of water" is to be read as "in normal operating conditions be capable of delivering at least the required jets of water", and
  2. The expression "at least the two jets of water required in paragraph 2.1.5.1" is to be read as "at least the required jets of water".

3.6.6.7 The fire pumps on vessels of less than 500 gross tonnage, other than passenger vessels that are Safety Convention vessels, are not required to meet the minimum capacity requirement of 25 m3/h set out in regulation 10.2.2.4.2.

3.6.7 Fire Hoses and Nozzles

3.6.7.1 In addition to the requirements of regulation 10.2.3.1.1, the fire hoses in a machinery space of category A or for a space that contains flammable materials must be connected to the fire hydrants at all times. If there is more than one fire hose in a machinery space of category A, one of the fire hoses in that space must also be connected to a portable foam applicator.

3.6.7.2 In addition to the requirements of regulation 10.2.3.1.1, every fire hose must be:

  1. Stowed in a space designed to permit deployment of the hose without it becoming entangled, and
  2. Stored in a manner that protects the hose from the anticipated low ambient temperatures.

3.6.7.3 The nozzles, couplings and fittings for the fire hoses on a tanker must be made of brass, bronze or other equivalent non-sparking material.

3.6.7.4 For the purposes of regulation 10.2.3.2.1:

  1. The design of the piping system must be taken into consideration in determining the number of fire hoses,
  2. The minimum diameter of a fire hose must be 38 mm, and
  3. Every fire hose must have the same diameter, but hoses in machinery spaces and other interior locations may have a smaller diameter than hoses in other locations if the smaller diameter is for the purpose of convenient handling.

3.6.7.5 For the purposes of regulation 10.2.3.3.3, if paragraph 3.6.4.1 applies and the number and position of hydrants on the vessel is such that only one jet of water may reach any part of the vessel, the expression "from two jets" is to be read as "from one jet".

3.6.8 Portable Fire Extinguishers

3.6.8.1 For the purposes of regulation 10.3.2.1, on a passenger vessel:

  1. Each main vertical zone below the bulkhead deck must be provided with the greater of:
    1. two portable water fire extinguishers of at least 9 L capacity each or two portable fire extinguishers of equivalent fire-extinguishing capability, and
    2. two portable fire extinguishers of a type described in subparagraph (i) for each 15 m, or fraction of 15 m, in length of the zone.
  2. Each main vertical zone on or above the bulkhead deck must be provided, on each side of the vessel, with one portable fire extinguisher of a type described in subparagraph (a)(i), and
  3. Despite paragraph (b), if the vessel is of 500 gross tonnage or less and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2, each main vertical zone on or above the bulkhead deck must be provided with one portable fire extinguisher of a type described in subparagraph (a)(i).

3.6.8.2 For the purposes of regulation 10.3.2.1, on a cargo vessel:

  1. a) The area within the outside boundary of each accommodation space below the bulkhead deck must be provided with the greater of:
    1. i. two portable water fire extinguishers of at least 9 L capacity each or two portable fire extinguishers of equivalent fire-extinguishing capability, and
    2. ii. two portable fire extinguishers of a type described in subparagraph (i) for each 15 m, or fraction of 15 m, in length of the area, and
  2. b) The area within the outside boundary of each accommodation space on or above the bulkhead deck must be provided with one portable fire extinguisher of a type described in subparagraph (a)(i) for each 15 m, or fraction of 15 m, in length of the area.

3.6.8.3 For the purposes of regulation 10.3.2.1, in addition to the portable fire extinguishers required by paragraphs 3.6.8.1and 3.6.8.2:

  1. One portable water fire extinguisher of at least 9 L capacity or one portable fire extinguisher of equivalent fire-extinguishing capability must be provided next to the access to each store-room for each 232 m2, or fraction of 232 m2, of surface area of the store-room,
  2. Each galley and each pantry that contains cooking facilities must be provided with one portable dry-chemical fire extinguisher of at least 4.5 kg capacity or one portable fire extinguisher of equivalent fire-extinguishing capability for each 232 m2, or fraction of 232 m2, of surface area of the galley or pantry, and
  3. Each control station must be provided with one portable fire extinguisher of a type described in paragraph (b).

3.6.8.4 Every portable fire extinguisher must be fitted with a clamp bracket that:

  1. Is designed to withstand the roll, pitch and vibration of the vessel, and
  2. Holds the fire extinguisher securely in place but provides quick and positive release of the fire extinguisher for immediate use.

3.6.8.5 Every wheeled-type portable fire extinguisher must be fitted with a metal clip arrangement that:

c) Is designed to withstand the roll, pitch and vibration of the vessel, and

d) Holds the fire extinguisher securely in place but provides quick and positive release of the fire extinguisher for immediate use.

3.6.8.6 Regulation 10.3.3 does not apply in respect of a vessel that is not a Safety Convention vessel and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.6.9 Types of Fixed Fire-extinguishing Systems

3.6.9.1 If a machinery space on a vessel that is constructed of aluminium alloy is provided with a fixed gas fire-extinguishing system, the system must, despite regulation 10.4.1.1.1, have a sufficient quantity of gas to provide two independent charges of gas.

3.6.10 Fire-extinguishing Arrangements in Machinery Spaces

3.6.10.1 Regulations 10.5.1.2.1, 10.5.2.2.1 and 10.5.3.2.1 do not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.6.10.2 The requirement in regulation 10.5.2.2.2 with respect to foam fire extinguishers of at least 45 L capacity each or equivalent does not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.6.10.3 Regulation 10.5.6 does not apply in respect of a vessel that is not a Safety Convention vessel and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.6.11 Spaces Containing Flammable Liquids

3.6.11.1 For the purpose of regulation 10.6.3.2, the fire-extinguishing arrangements must include fixed gas fire-extinguishing systems, fixed foam fire-extinguishing systems and fixed pressure water-spraying f ire-extinguishing systems that meet the requirements of the FSS Code for the system.

3.6.12 Fixed Gas Fire-extinguishing Systems for General Cargo

3.6.12.1 For the purpose of regulation 10.7.1.2, the expression "it is shown to the satisfaction of the Administration that a passenger ship is engaged on voyages of such short duration that it would be unreasonable to apply the requirements of paragraph 7.1.1" is to be read as "a passenger ship is engaged on voyages of not more than 48 hours' duration during which the cargo holds are opened to discharge or receive cargo."

3.6.13 Fire-fighters' Outfits

3.6.13.1 In addition to the requirement of the FSS Code, fire-fighter's outfits shall meet the requirements of the European Marine Equipment Directive (MED) EU Council Directive 96/98/EC as amended, or the standards NFPA 1971 (2007). The self-contained breathing apparatus (SCBA) shall meet the MED, the NFPA 1981(2007) standard or the National Institute and Occupational Safety and Health (NIOSH) requirements, and be rated for use in fighting fires. Pressure containers shall meet the requirements of the Transportations of Dangerous Goods Regulations.

3.6.13.2 Regulations 10.10.2.1 and 10.10.2.2 do not apply in respect of a vessel that is not a Safety Convention vessel, is of less than 500 gross tonnage and, if the vessel is not a cargo vessel, is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.6.13.3 Regulation 10.10.2.3 applies only in respect of tankers of 500 gross tonnage or more.

3.6.14 Fire Axes

3.6.14.1 In addition to the requirements of regulation 10, a passenger vessel on a near coastal voyage, Class 1 or an unlimited voyage must be provided with the greater of:

  1. Three fire axes, and
  2. One fire axe for each 15 m, or fraction of 15 m, in length of the vessel.

3.6.14.2 In addition to the requirements of regulation 10, a passenger vessel on a sheltered waters voyage or a near coastal voyage, Class 2 must be provided with:

  1. If the vessel is of 24 m or more in length but of less than 500 gross tonnage, two fire axes, and
  2. If the vessel is of 500 gross tonnage or more, one fire axe for each 15 m, or fraction of 15 m, in length of the vessel.

3.6.14.3 In addition to the requirements of regulation 10, a cargo vessel must be provided with:

  1. If the vessel is of 24 m or more in length but of less than 500 gross tonnage, two fire axes, and
  2. If the vessel is of 500 gross tonnage or more, three fire axes.

3.7 Regulation 12 - Notification of Crew and Passengers

3.7.1 Public Address Systems

3.7.1.1 The public address system or other means of communication required by regulation 12.3 must be available on all vessels throughout the spaces referred to in that regulation, the muster stations, the embarkation stations and the machinery spaces.

3.8 Regulation 13 - Means of Escape

3.8.1 Passenger Vessels

3.8.1.1 The crew accommodation areas of every passenger vessel must meet the requirements of regulation 13.3.2.5.1.

3.8.1.2 Each escape hatch must be painted orange and be operable from both sides of the hatch.

3.8.2 Cargo Vessels

3.8.2.1 Every cargo vessel must meet the requirements of regulation 13.3.2.5.1, and the crew accommodation areas of the vessel must also meet those requirements.

3.8.2.2 Each escape hatch must be painted orange and be operable from both sides of the hatch.

3.8.2.3 Every cargo vessel must meet the requirements of regulation 13.3.2.6.2.

3.8.2.4 The means of escape required by regulation 13.3.3.1 must be separated so as to minimize the possibility of their being blocked at the same time as a result of an incident.

3.8.2.5 Each means of escape required by regulation 13.3.3.2 must give direct access to a means of escape on the deck above.

3.8.2.6 On a cargo vessel of 500 gross tonnage or more, if one of the means of escape required by regulation 13.3.3.2 or 13.3.3.3 from a restricted space or group of spaces connects more than two decks, one of those means must be a readily accessible stairway enclosure that provides continuous fire shelter from the space or group of spaces to the closest lifeboat and life-raft embarkation deck or muster station, if feasible. If the stairway enclosure is not feasible, details must be provided which demonstrate the route by which the crew can escape from any deck to the embarkation station without entering any space where the fire may be located, the details must clearly show that the route is protected from the fire by A class bulkheads for its whole length.

3.8.2.7 Above the lowest open deck, if the two means of escape required by regulation 13.3.3.3 are widely separated doors to the open deck, a stairway enclosure that provides continuous fire shelter is not required.

3.8.2.8 Despite regulation 13.3.3.2, if it is not feasible to install a stairway or trunk is not feasible, a vertical ladder may be used as the second means of escape from crew spaces that are entered only occasionally.

3.8.2.9 Despite regulation 13.3.3.3, if installing a stairway is not feasible, a vertical ladder may be used as one of the means of escape from crew spaces that are entered only occasionally.

3.8.3 Emergency Escape Breathing Devices

3.8.3.1 Regulation 13.4.3 does not apply in respect of a vessel that is not a Safety Convention vessel, is of 500 gross tonnage or less and is engaged on a sheltered waters voyage or a near coastal voyage, Class 2.

3.8.3.2 The emergency escape breathing devices (EEBD) required by regulation 13.4.3 and for which that regulation requires compliance with the FSS Code must be of a type approved by the Minister as meeting the applicable requirements of that Code.

3.8.3.3 In addition to the requirement of the FSS Code, EEBD shall meet the requirements of European Marine Equipment Directive (MED) EU Council Directive 96/98/EC as amended, or the National Institute and Occupational Safety and Health (NIOSH) requirements. Pressure containers shall meet the requirements of the Transportations of Dangerous Goods Regulations.

3.8.4 Additional Requirements for Ro-Ro Passenger Vessels

3.8.4.1 Any words included in the symbols required by regulation 13.7.1.1 to mark the escape routes must be printed in English and French.

3.8.5 Instruction for Safe Escape

3.8.5.1 Every vessel must display "mimic" plans in accordance with regulation 13.7.2.2 and must also display those plans in every space occupied by the crew.

3.8.5.2 Any words on the "mimic" plans must be printed in English and French.

3.9 Regulation 15 - Instructions, On-Board Training and Drills

3.9.1 Training Manuals

3.9.1.1 If a vessel is fitted with a fixed gas fire-extinguishing system, the instructions on fire-fighting activities and fire-fighting procedures required by regulation 15.2.3.4.2 must include instructions on the use of fire-fighters' outfits, including breathing apparatus, and the protected space re-entry procedure recommended by the manufacturer of the system.

3.9.2 Fire Control Plans

3.9.2.1 The plans and booklets required by regulation 15.2.4 must be:

  1. In the working language of the vessel, and
  2. In English or French, or in both languages, according to the needs of the shore-side fire-fighting personnel.

3.9.3 Fire Drills

3.9.3.1 Regulations 15.2.1, 15.2.2 and 15.3.1 do not apply in respect of vessels to which the Fire and Boat Drills Regulations apply.

3.10 Regulation 17 - Alternative Design and Arrangements

3.10.1.1 An engineering analysis submitted under regulation 17.3 must be written in English or French.

3.11 Regulation 18 - Helicopter Facilities

3.11.1 Helicopter Refueling and Hangar Facilities

3.11.1.1 The "NO SMOKING" signs required by regulation 18.7.10 must be in English and French as well as in the working language of the vessel.

3.11.2 Operations Manual

3.11.2.1 The operations manual required by regulation 18.8.1 must be in the working language of the vessel.

3.12 Regulation 20 - Protection of Vehicle, Special Category and Ro-Ro Spaces

3.12.1 Structural Protection

3.12.1.1 The requirements of regulation 20.5 apply in respect of all passenger vessels.

3.12.2 Fire Extinction

3.12.2.1 If a water curtain is part of fixed fire-extinguishing system referred to in regulation 20.6.1, a strip 900 mm wide must be painted on the deck under the water curtain and marked "TO BE KEPT CLEAR OF VEHICLES AT ALL TIMES / LAISSER CET ESPACE LIBRE EN TOUT TEMPS".

3.12.2.2 Each portable fire extinguisher required by regulation 20.6.2.1 must be a portable dry-chemical fire extinguisher of at least 4.5 kg capacity or a portable fire extinguisher of equivalent fire-extinguishing capability.

3.12.2.3 In the case of a vessel that is not a Safety Convention vessel and that is engaged on a sheltered waters voyage or a near coastal voyage, Class 2, the reference in regulation 20.6.2.2.1 to the word "three" is to be read as a reference to the word "one".

Previous Page | Next Page