7.1.1 This section applies to all gasoline and diesel fuel systems for all small vessels, except where indicated otherwise.
7.2.1 A permanently installed fuel system shall provide protection from leakage caused by corrosion, shock, or fire.
7.2.2 All components of a fuel system, including tank penetrations and fittings, shall be accessible for inspection.
7.2.3 After installation, the fuel system, which includes fill pipes, tanks, vent pipes, delivery pipes, and return pipes, shall be hydrostatically pressure tested to a minimum of 21 kPa (3 lbs/in2).
7.2.4 The fuel system shall be designed and installed to contain at least 5% fuel expansion to minimize the risk of a fuel spill either into the vessel or the environment when:
7.2.5 Fuel systems shall be liquid and vapour tight to the hull interior, except when:
7.2.6 Fuel systems shall be capable of:
7.2.7 Fuel tank, fuel filter, or fuel line fittings shall not be installed over a source of ignition. Personal watercraft are exempt from this requirement.
7.2.8 All electrically operated components installed in GASOLINE fuel systems shall be ignition-protected.
7.2.9 Every drain plug or valve on every filter or fuel tank of a DIESEL system shall be:
7.2.10 Metal bowls shall be used for inboard GASOLINE engines and plastic bowls shall be used for outboard engines. Every fuel-water separator bowl used for gasoline engines must meet the requirement of National Fire Protection Association NFPA 302, Fire Protection Standard for Pleasure and Commercial Motor Craft
7.2.11 Every hose in a fuel system shall meet or exceed:
7.2.12 Every hose shall be permanently marked in capital letters and numerals at least 3 mm (0.12 in) in height and width and at intervals not greater than 305 mm (12 in) with the following information:
7.2.12.1 Hoses less than 305 mm (12 in) in length may be tagged with the required marking.
7.3.1.1 Every fuel tank shall be constructed to meet the minimum test requirements for mechanical strength and fire resistance, as detailed in ABYC Standards for Small Craft H-24, Gasoline Fuel Systems, or ABYC Standards for Small Craft H-33, Diesel Fuel Systems, as applicable.
7.3.1.2 A metallic fuel tank shall be constructed of materials in accordance with Table 7-1. Non-metallic materials are considered acceptable for corrosion resistance; however, all other requirements of this Standard must be met.
7.3.1.3 A fuel tank shall be constructed so that no external surface of the tank can retain moisture or spilled fuel.
7.3.1.4 A GASOLINE fuel tank shall have no openings in the bottom, sides, or ends.
7.3.1.5 Clean-out plates shall not be installed in GASOLINE fuel tanks; clean-out plates may be installed in the top or sides of DIESEL fuel tanks.
| Material |
Specification Sheet Thickness |
Minimum Nominal |
Gauge Processes (1) |
Welding |
|---|---|---|---|---|
| Nickel-Copper |
ASTM - B127 Class A |
0.79 mm | 22 U.S. std | Resistance Seam; Inert Gas Shielded Arc; Oxyacetylene |
| Copper-Nickel | ASTM - B122 | 1.14 mm | 17 AWG |
Inert Gas Shielded Arc; Oxyacetylene; Resistance |
| Copper (2) |
ASTM - B152 Type E.T.P. |
1.45 mm | 15 AWG |
Inert Gas Shielded Arc; Carbon Arc; Oxyacetylene |
| Copper-Silicon |
ASTM - B97 Types A, B & G |
1.27 mm | 16 AWG |
Inert Gas Shielded Arc; Carbon Arc; Oxyacetylene; Metal-Arc |
| Steel Sheet (3) | ASTM - A93 | 1.90 mm | 14 Mfrs. |
Metal-Arc; Oxyacetylene; Inert Gas Shielded Arc; Resistance |
| Aluminized Steel (5) | ASTM - A463 | 1.21 mm | 18 Mfrs. |
Metal-Arc; Oxyacetylene; Inert gas Shielded Arc; Resistance |
| Aluminum (4) | Alloy 5052 or 5083 or 5086 | 2.29 mm | - | Inert Gas Shielded Arc; Resistance |
| Stainless Steel | 316 L | 0.79 mm | 22 U.S. std. | Metal-Arc; Oxyacetylene; Inert Gas Shielded Arc; Resistance |
Notes
7.3.1.6 If baffles are provided, baffle openings shall be designed so that they do not prevent the fuel flow across the bottom or trap vapour across the top of the tank.
7.3.1.7 Threaded connections into fuel tanks shall be in accordance with American National Standard Taper Pipe Thread (NPT).
7.3.1.8 Cellular plastic used to encase metallic fuel tanks shall not change volume by more than 5% or dissolve after being immersed for 24 hours at 29°C in each of the following liquids:
reference fuel B, in accordance with American Society of Testing and Materials ASTM D471, Standard Test Method for Rubber Property - Effects of Liquid;
No. 2 reference oil, in accordance with American Society of Testing and Materials ASTM D471, Standard Test Method for Rubber Property - Effects of Liquid; and
a 5% solution of trisodium phosphate in water.
7.3.1.9 Cellular plastic used to encase metallic fuel tanks shall not absorb more than 0.58 kg (0.1 lbs.) of water per square metre (ft2) of cut surface.
7.3.1.10 Where plastic is bonded to a metallic tank, the adhesive strength of the bond shall exceed the cohesive strength of the plastic.
7.3.1.11 Non-polyurethane cellular plastic used to encase metallic fuel tanks shall have a minimum compressive strength of 410 kPa (60 lbs/in2) at a 10% deflection, measured in accordance with American Society of Testing and Materials ASTM D1622, Standard Test Method for Apparent Density of Rigid Cellular Plastics.
7.3.1.12 Polyurethane cellular plastic, which is used to encase metallic fuel tanks, shall have a minimum density of 50 kg/m3 (3 lbs/ft3) measured in accordance with American Society of Testing and Materials ASTM D1622.
7.3.1.13 Rigid tubes and fill pipes that extend near the bottom of the tank shall have clearance to prevent contact with the bottom due to flexing of the tank.
7.3.1.14 Every fuel tank shall have permanently affixed to it a label showing as a minimum:
7.3.1.14.1 Note: In lieu of the requirements of 7.3.1.1 to 7.3.1.13, the design and construction of the fuel tank may conform to an equivalent standard to those requirements, e.g. United States Government; CFR33, 183.510 (a).
7.3.1.15 Every letter and numeral on any fuel tank shall be:
7.3.1.16 Every tank label shall be readily visible and legible on the tank as installed.
7.3.2.1 Every fuel tank, including those encased in cellular plastic foam or fibre reinforced plastic, shall be so installed that all connections, accessories, and labels are accessible for inspection and maintenance.
7.3.2.2 A GASOLINE fuel tank shall not be made integral with the hull.
7.3.2.3 No fuel tank shall support any deck, bulkhead, or structural component, or bear any extraneous load unless it is designed and built to do so.
7.3.2.4 Adequate supports shall be fitted as necessary to ensure the structural integrity of every tank.
7.3.2.5 A fuel tank shall be installed and restrained to provide as close to no movement as possible.
7.3.2.6 Metallic fuel tank supports and hold-downs shall be isolated from the tank surface by non-abrasive, non-absorbent and non-conductive materials.
7.3.2.7 Cellular plastic shall not be used as the sole support for a metal fuel tank.
7.3.2.8 Cellular plastic used as the sole support for a non-metallic fuel tank shall meet the requirements of American Society of Testing and Materials ASTM D1621, Standard Test Method for Compressive Properties of Rigid Cellular Plastic, or American Society of Testing and Materials ASTM D1622, Standard Test Method for Apparent Density of Rigid Cellular Plastic.
7.3.2.9 No cellular or fibre reinforced plastic fuel tank encasement shall permit water to:
7.3.2.10 Metallic fuel tanks installed above a flat surface shall be separated from the surfaces by at least a 6 mm (1/4 in) air space when filled with fuel.
7.3.3.1 Every fuel tank shall be installed with mechanical or remote reading fuel gauges, unless the tank installation permits sounding.
7.3.4.1 Fuel fill lines shall be hose or metal pipe.
7.3.4.2 Each fuel tank shall have an individual fill line.
7.3.4.3 Deck fill plates:
7.3.4.4 Fuel shall not blow back through the fuel fitting when the tank is being refueled at a rate of 23 L/min (6 U.S. gal/min).
7.3.4.5 The fill pipe installation shall be self-draining and lead directly from the deck fill to the tank in such a way as to prevent any vapour locks.
7.3.4.6 The minimum inside diameter of the fill system shall be 32 mm (11/4 in) In order to maintain the minimum diameter, the minimum hose ID using standard fittings shall be 38 mm (11/2 in).
7.3.4.7 The hose in a fuel tank fill system shall be secured to the deck fill and the tank with corrosion resistant and galvanically compatible fittings consisting of:
7.3.4.8 Every hose clamp used in a tank fill system shall:
7.3.4.9 Fuel fill hose shall be of neoprene fabric or wire reinforced neoprene material that meets the requirements for fuel hose in 7.2.11 and 7.2.12.
7.3.4.10 Every fuel fill hose installed in the engine compartments shall be USCG Type A1 or A2.
7.3.4.11 Fuel hose shall not be installed on helical threading or knurling that provides a path for fuel leakage.
7.3.5 Fuel Tank Venting Systems
7.3.5.1 Every fuel tank shall have a venting system that:
7.3.5.2 Every flexible vent pipe shall be:
7.3.5.3 The vent shall be fitted with a flame arrestor that:
7.3.5.4 Tank vent systems shall be self-draining and connect to the highest point of the fuel tank as installed in the vessel under conditions of normal operation and normal trim.
7.4.1
7.4.2 Every metallic fuel line:
7.4.3 A metallic fuel line shall be attached to the vessel structure within 102 mm (4 in) of the connection of a flexible fuel line.
7.4.4 A section of flexible line with sufficient slack to absorb vibration shall be installed where a rigid fuel line terminates at:
7.4.5 The inside diameter of a hose shall not exceed the minimum outside diameter of the connecting spud, pipe, or fitting by more than the tolerance shown in Table 7-2.
| Minimum Outside Diameter of the Fitting | Tolerance of Inside Diameter of Hose |
|---|---|
| Less than 9.5 mm (3/8 in) | 0.51 mm (0.020 in) |
| 9.5 mm to 25 mm (3/8 in to 1 in) | 0.89 mm (0.035 in) |
| Greater than 25 mm (1 in) | 1.65 mm (0.065 in) |
7.4.6 All fuel distribution systems shall be provided with anti-siphon protection by at least one of the following:
7.4.6.1 Note: Readily accessible from outside, the compartment includes a shut-off valve installed at the tank, close to, and directly below, an access port in the deck through which the valve can be operated.
7.4.7 If the length of fuel line from the tank outlet to the engine inlet is greater than 3600 mm (11 ft 10 in), a second manual shut-off valve shall be installed at the fuel inlet connection to the engine.
7.4.8 Fuel systems shall be equipped with an independently supported fuel strainer or filter, complying with subsection 7.5, if a strainer or filter is not incorporated in the pick-up tube.
7.4.9 On vessels with multiple fuel tanks and a fuel system that returns fuel to the tank (such as fuel injection), the system shall return unused fuel to the same tank from which it was drawn.
7.4.10 The design and construction of the fuel system requires a warning label indicating that modifying this system may result in a fuel overflow. See ABYC Standards for Small Craft T-24, Owner/Operator's Manuals.
7.5.1 Every fuel system fitting, joint, and connection shall be accessible for inspection, maintenance, and removal, without the removal of any permanent vessel structure.
7.5.2 Fuel lines shall have the minimum number of connections practicable.
7.5.3 Hoses used in the fuel tank fill system shall be secured to pipes (smooth pipes acceptable), spuds, or other fittings at each connection, by at least two (2) metallic clamps with nominal band widths of at least 12 mm (1/2 in).
7.5.4 Every hose used in the fuel tank vent system or the fuel distribution and return line system shall be secured to a mating spud, pipe, or fitting that is formed or machined to provide serrations (at least 0.38 mm [0.15 in] depth) or a bead. At least one corrosion resistant metallic clamp shall be used with a minimum nominal band width. (Table 7-3)
| Outside Diameter of Hose | Clamp Width |
|---|---|
| Less Than 11 mm (7/16 in) | 6 mm (1/4 in) |
| 11 mm to 20 mm (7/16 in. to 25/32 in) | 8 mm (3/8 in) |
| Greater than 20 mm (25/32 in) | 12.5 mm (1/2 in) |
7.5.5 Every clip, strap, or hose clamp, including fasteners:
7.5.6 Every hose clamp:
7.5.7 The minimum nominal band width of every hose clamp shall be determined by the outside diameter of the hose, as shown in Table 7-3.
7.5.8 A gasoline fuel system shall not have a fitting for draining fuel other than a plug that is used to service the fuel filter or strainer and that:
7.6.1 Valves shall pass the 2.5-minute fire test as specified in United States Government CFR 33, Section 183.590 and ABYC Standards for Small Crafts H-24.5.7.
7.6.2 Electrically operated valves shall meet the requirements of Underwriters Laboratories UL 429, Electrically Operated Valves.
7.6.3 The unit shall incorporate means for independent mounting designed to relieve strain from connected fuel lines.
7.6.4 Manually operated valves shall be designed with positive stops in the open and closed positions, or shall indicate their opened and closed positions.
7.6.5 Electrically operated shut-off valves shall be connected to be energized to open when the engine ignition switch is on. A provision for manual operation shall be incorporated in the design.
7.6.6 Tapered plug valves with an external spring shall not be used.
7.7.1 Every fuel filter or strainer shall meet the fire resistance requirements for fuel systems set forth in ABYC Standards for Small Craft H-24.5.7, unless the filter or strainer is inside the fuel tank.
7.7.2 All fuel filters or strainers shall be supported on the engine or vessel structure independent from the fuel line connections, unless the filter or strainer is inside the fuel tank.
7.7.3 Filters, separators, and strainers shall meet the requirements of Underwriters Laboratories UL 1105, Standard for Marine Use Filters, Strainers, and Separators.
7.7.4 Fuel tank withdrawal pipes that are fitted with fuel filters:
7.8.1 Every fuel pump shall be installed on the engine or within 305 mm (12 in) of the engine, with a maximum delivery hose length of 1220 mm (48 in) unless it is a fuel pump used to transfer fuel
7.8.2 A diaphragm pump shall not leak fuel if the primary diaphragm fails.
7.8.3 Every electric fuel pump shall incorporate an automatic cutoff designed to eliminate fuel pressure at the outlet when the engine stops for any cause.
7.8.4 The outlet pressure of electrically operated fuel pumps, except for electric fuel pumps used to transfer fuel between tanks, shall be rated or controlled to the maximum carburetor fuel inlet pressure specified by the engine manufacturer.
7.8.5 A momentary type switch may override the automatic cutoff for the purpose of priming or starting the engine.
7.9.1 Each metal or metallic plated component of the fuel fill system and fuel tank that is in contact with the fuel must be grounded so that its resistance to the vessel ground is less than 1 ohm.
7.9.2 Ground wire ends shall not be clamped between the fill pipe and hose.
7.9.3 Static conductive neoprene tubing or piping that is used in lieu of metallic conductors shall be:
7.10.1 Every carburetor, when tested to the requirements of the fire resistance test set forth in ABYC Standards for Small Craft H-24, Appendix A, shall not leak more than 5 mL of fuel in 30 seconds when:
7.10.2 Every up-draught and horizontal-draught carburetor shall have a device that:
7.10.3 Every engine shall be equipped with an effective means of backfire flame control by the use of an effective flame arrestor.
7.10.4 Every inboard engine that uses a carburetor shall be so designed and fitted as to prevent gasoline from leaking into the bilge.
7.11.1 A warning label shall be placed in a readily visible location on the vessel, or at a point of frequent servicing of the vessel. Labelling shall not weaken the tank.
7.11.2 The label shall comply with ABYC Standards for Small Craft T-5, “Safety, Signs and Labels,” and shall contain at least the following informational elements:
Figure 7-1. Example of Warning Label
WARNING
AVOID SERIOUS INJURY OR DEATH FROM FIRE OR EXPLOSION RESULTING FROM LEAKING FUEL. INSPECT SYSTEM FOR LEAKS AT LEAST ONCE A YEAR.
7.11.3 Each valve in the fuel system shall be clearly marked with its function and with what each position means.
7.12.1 The following additional requirements apply to all outboard installations.
7.12.2 All permanent fuel lines in outboard motor vessels shall terminate adjacent to the transom, so that any leakage will not enter the vessel.
7.12.3 Quick disconnect fittings used between fuel distribution lines and outboard motors shall automatically shut off fuel flow when disconnected.
7.12.4 No pressurized tanks shall be built into or be permanently attached to any hull.